Dry-Type SC(B)13-30~2500/10/0.4 Transformer

Home > Products > Dry-Type Transformer > Dry-Type SC(B)13-30~2500/10/0.4 Transformer

Dry-Type SC(B)13-30~2500/10/0.4 Transformer

  • Brand Hengda
  • Model No. SC(B)13-30~2500/10/0.4
  • Phase 3 Phases
  • Vector Group/Connection Type Yyn0 or Dyn11
  • Tap Ranger ±5% or ±2*2.5%
  • Frequency 50HZ/60HZ
  • Coil Material Copper/Aluminum
Get Free Quote


Resin insulated dry-type transformer, due to the coil is encapsulated by epoxy resin, so it is flame retardant, fireproof, explosion-proof, maintenance-free, non-polluting, small in size, and can be directly placed in the load center. Due to the scientific and reasonable design and casting process, the product has smaller partial discharge, low noise, strong heat dissipation ability, and can be operated for a long time under 125% of the rated load under the condition of forced air-cooling, and is equipped with a temperature controller, which has the functions of fault alarm, over-temperature alarm, over-temperature trip, and black-box function, and is connected to the computer through the RS485 serial interface to enable centralized monitoring and control.

Rated Power
(kVA)
Voltage Combination Vector Group/
Connection Method
No-Load Loss Load Loss Short-circuit Impedance No-load Current
H.V(kV) H.V. Tap Range(%) L.V(kV) W W % %
30 6
6.3
10
10.5
11
±5%
or±2*2.5%
0.4 Dyn11 135 640 4 2
50 195 900 2
80 265 1240 1.5
100 290 1410 1.5
125 340 1660 1.3
160 385 1910 1.3
200 445 2270 1.1
250 515 2480 1.1
315 635 3120 1
400 705 3590 1
500 835 4390 1
630 935 5360 6 0.85
800 1090 6260 0.85
1000 1270 7310 0.85
1250 1500 8720 0.85
1600 1760 10500 0.85
2000 2190 13000 0.7
2500 2590 15400 0.7
Operating Condition: 1.Altitude not exceeding 1000 meters
2.Maximum ambient temperature +40°C
3.Maximum daily average temperature +30°C
4.Maximum annual average temperature +20°C
5.Maximum low temperature-25°C
6.Transformers for operation under special conditions are available upon request.

 

Features:

Low-voltage winding: Low-voltage winding adopts foil structure, which solves the problem of axial helix angle when winding with wire and makes the ampere-turns more balanced, meanwhile, the coil adopts axial cooling duct to enhance the heat dissipation ability, and epoxy resin is adopted between the winding layers, and the whole is cured and shaped.

The core is made of imported high-quality cold-rolled silicon steel sheet, the core column is tied with F-class latitude-free tape, and the surface of the core is encapsulated with epoxy resin, which reduces the no-load loss, no-load current and noise of the core.

The clamps and fasteners are treated with special surface treatment, which further improves the product appearance quality.

Adopting cross-flow side-blowing cooling fan, the cooling fan has the characteristics of low noise, high wind pressure, beautiful appearance, etc., which enhances the overload capacity of the transformer. Temperature control adopts only temperature controller, which improves the reliability of transformer operation.

 

For other specifications, voltage, capacity, customized requirements and more details, please kindly send us an email!!!

 

Top