Dry-Type 30kVA-500kVA Transformer

Home > Products > Dry-Type Transformer > Dry-Type 30kVA-500kVA Transformer

Dry-Type 30kVA-500kVA Transformer

  • Brand Hengda
  • Model No. 30kVA to 500kVA
  • Phase 3 Phases
  • Vector Group/Connection Type Yyn0 or Dyn11
  • Tap Ranger ±5% or ±2*2.5%
  • Frequency 50HZ/60HZ
  • Coil Material Copper/Aluminum
Get Free Quote

Description


Resin insulated dry-type transformer, due to the coil is encapsulated by epoxy resin, so it is flame retardant, fireproof, explosion-proof, maintenance-free, non-polluting, small in size, and can be directly placed in the load center. Due to the scientific and reasonable design and casting process, the product has smaller partial discharge, low noise, strong heat dissipation ability, and can be operated for a long time under 125% of the rated load under the condition of forced air-cooling, and is equipped with a temperature controller, which has the functions of fault alarm, over-temperature alarm, over-temperature trip, and black-box function, and is connected to the computer through the RS485 serial interface to enable centralized monitoring and control.

SC(B)11-10kV Technical Specifications

Rated Power
(kVA)
Voltage Combination Vector Group/
Connection Method
No-Load Loss Load Loss Short-circuit Impedance No-load Current
H.V(kV) H.V. Tap Range(%) L.V(kV) W W % %
30 6
6.3
10
10.5
11
±5%
or±2*2.5%
0.4 Dyn11 170 710 4 2
50 240 1000 2
80 330 1380 1.5
100 360 1570 1.5
125 420 1850 1.3
160 480 2130 1.3
200 550 2530 1.1
250 640 2760 1.1
315 790 3470 1
400 880 3990 1
500 1040 4880 1
630 1170 5960 6 0.85
800 1360 6960 0.85
1000 1590 8130 0.85
1250 1880 9690 0.85
1600 2200 11700 0.85
2000 2740 14400 0.7
2500 3240 17100 0.7
Operating Condition:   1.Altitude not exceeding 1000 meters
2.Maximum ambient temperature +40°C
3.Maximum daily average temperature +30°C
4.Maximum annual average temperature +20°C
5.Maximum low temperature-25°C
6.Transformers for operation under special conditions are available upon request.

 

Features:

  • Low-voltage winding: Low-voltage winding adopts foil structure, which solves the problem of axial helix angle when winding with wire and makes the ampere-turns more balanced, meanwhile, the coil adopts axial cooling duct to enhance the heat dissipation ability, and epoxy resin is adopted between the winding layers, and the whole is cured and shaped.
  • The core is made of imported high-quality cold-rolled silicon steel sheet, the core column is tied with F-class latitude-free tape, and the surface of the core is encapsulated with epoxy resin, which reduces the no-load loss, no-load current and noise of the core.
  • The clamps and fasteners are treated with special surface treatment, which further improves the product appearance quality.
  • Adopting cross-flow side-blowing cooling fan, the cooling fan has the characteristics of low noise, high wind pressure, beautiful appearance, etc., which enhances the overload capacity of the transformer. Temperature control adopts only temperature controller, which improves the reliability of transformer operation.

For other specifications, voltage, capacity, customized requirements and more details, please kindly send us an email!!!

Top