Dry-Type SC(B)18-30~2500/10/0.4-NX2 Transformer

Home > Products > Dry-Type Transformer > Dry-Type SC(B)18-30~2500/10/0.4-NX2 Transformer

Dry-Type SC(B)18-30~2500/10/0.4-NX2 Transformer

  • Brand Hengda
  • Model No. SC(B)18-30~2500/10/0.4
  • Phase 3 Phases
  • Vector Group/Connection Type Yyn0 or Dyn11
  • Tap Ranger ±5% or ±2*2.5%
  • Frequency 50HZ/60HZ
  • Coil Material Copper/Aluminum
Get Free Quote


The product meets China’s national first level energy efficiency standards.Resin insulated dry-type transformer, due to the coil is encapsulated by epoxy resin, so it is flame retardant, fireproof, explosion-proof, maintenance-free, non-polluting, small in size, and can be directly placed in the load center. Due to the scientific and reasonable design and casting process, the product has smaller partial discharge, low noise, strong heat dissipation ability, and can be operated for a long time under 125% of the rated load under the condition of forced air-cooling, and is equipped with a temperature controller, which has the functions of fault alarm, over-temperature alarm, over-temperature trip, and black-box function, and is connected to the computer through the RS485 serial interface to enable centralized monitoring and control.

Rated Power
(kVA)
Voltage Combination Vector Group/
Connection Method
No-Load Loss Load Loss Short-circuit Impedance No-load Current
H.V(kV) H.V. Tap Range(%) L.V(kV) W W % %
30 6
6.3
10
10.5
11
±5%
or±2*2.5%
0.4 Yyn0   or Dyn11      105 640 4 2
50 155 900 2
80 210 1240 1.5
100 230 1415 1.5
125 270 1665 1.3
160 310 1915 1.3
200 360 2275 1.1
250 415 2485 1.1
315 510 3125 1
400 570 3590 1
500 670 4390 1
630 775 5290 0.85
630 750 5365 6 0.85
800 875 6265 0.85
1000 1020 7315 0.85
1250 1205 8720 0.85
1600 1415 10555 0.85
2000 1760 13005 0.7
2500 2080 15445 0.7
Operating Condition: 1.Altitude not exceeding 1000 meters
2.Maximum ambient temperature +40°C
3.Maximum daily average temperature +30°C
4.Maximum annual average temperature +20°C
5.Maximum low temperature-25°C
6.Transformers for operation under special conditions are available upon request.

 

Features:

Low-voltage winding: Low-voltage winding adopts foil structure, which solves the problem of axial helix angle when winding with wire and makes the ampere-turns more balanced, meanwhile, the coil adopts axial cooling duct to enhance the heat dissipation ability, and epoxy resin is adopted between the winding layers, and the whole is cured and shaped.

The core is made of imported high-quality cold-rolled silicon steel sheet, the core column is tied with F-class latitude-free tape, and the surface of the core is encapsulated with epoxy resin, which reduces the no-load loss, no-load current and noise of the core.

The clamps and fasteners are treated with special surface treatment, which further improves the product appearance quality.

Adopting cross-flow side-blowing cooling fan, the cooling fan has the characteristics of low noise, high wind pressure, beautiful appearance, etc., which enhances the overload capacity of the transformer. Temperature control adopts only temperature controller, which improves the reliability of transformer operation.

 

For other specifications, voltage, capacity, customized requirements and more details, please kindly send us an email!!!

Top