Oil-filled transformers use liquids for cooling, making them highly suitable for outdoor applications. They are more efficient, have longer service lives, and feature more reliable overload capabilities.Transformer is isolated from the rest of the air, to prevent and slow the deterioration of oil and insulation aging, enhance the operation reliability.

S11-10kV Technical Specifications

Rated Power Voltage Combination Vector Group/ No-Load Loss Load Loss(W) Impedance No-load Current
(kVA) H.V(kV) H.V. Tap Range(%) L.V(kV) Connection Method W Yy Dy % %
30 6 ±5% 0.4 Yyn0 100 600 630 4 1.5
50 6.3 or±2*2.5% or Dyn11 130 870 910 1.3
63 10 150 1040 1090 1.2
80 10.5 180 1250 1310 1.2
100 11 200 1500 1580 1.1
125 240 1800 1890 1.1
160 280 2200 2310 1
200 340 2600 2730 1
250 400 3050 3200 0.9
315 480 3650 3830 0.9
400 570 4300 4520 0.8
500 680 5150 5410 0.8
630 810 6200 6200 4.5 0.6
800 980 7500 7500 0.6
1000 1150 10300 10300 0.6
1250 1360 12000 12000 0.5
1600 1640 14500 14500 0.5
2000 1940 18300 18300 5 0.4
2500 2290 21200 21200 0.4
Operating Condition: 1.Altitude not exceeding 1000 meters
                                2.Maximum ambient temperature +40°C
                                3.Maximum daily average temperature +30°C
                                4.Maximum annual average temperature +20°C
                                5.Maximum low temperature-25°C
                                6.Transformers for operation under special conditions are available upon request.

 

Features:

  • The company produces three-phase oil-immersed distribution transformers with high efficiency and low loss, which can save a lot of power consumption and operating costs.
  • The transformer body adopts a new insulation structure, which improves the short-circuit resistance.
  • The transformer core is made of high-quality cold-rolled silicon steel sheets with high magnetic conductivity.
  • The transformer core consists of high/low-voltage windings are selected high-quality oxygen-free copper wire, and multi-layer cylindrical structure.
  • All fasteners with special anti-loosening treatment.
  • The oil tank is corrugated structure, the cover and the edge of the box are completely welded or fastened with bolts in two types, which fundamentally prolongs the service life of the transformer oil and insulating materials.